Fit

Fit

50 kW/112.53kWh, 80kW/160.76kWh, 100kW/208.98kWh
Tool-Free Manual Stacking, Flexible Multi-Rack Expansion, C4-M Corrosion Protection, Cost-Effective Air Cooling

Certifications

IEC/EN 62109-1/-2, IEC/EN 61000-6-2/-4, EN 50549-1&2/EN 50549-10, VDE-AR-N 4105, NTS 631, CEI 0-21, C10/11, NRS 097-2-1, TOR, G99, IEC 62116, IEC 61727, MEA, PEA, etc.*

Technical Specifications

Main Parameters

Cell
314 Ah LFP
Capacity
50 kW/112.53kWh, 80kW/160.76kWh, 100kW/208.98kWh
Rate
≤0.5 P
PCS

Detailed Parameters

 

TWS FIT Series modular stackable battery energy storage system with integrated air cooling fans

TWS FIT Commercial Hybrid Inverter Unit

Rack Parameters

 Fit-110Fit-160Fit-200
Cell typeLFP 314Ah
Pack configuration1P16S
Pack rated voltage51.2V
Pack dimensions (W*H*D)445mm * 808.5mm * 227.5mm
Pack capacity16.07kWh
Pack quantity71013
Rack capacity112.53kWh160.76kWh208.98kWh
Rack rated voltage358.4V512V665.6V
Rack voltage range313.6V ~ 397.6V448V ~ 568V582.4V ~ 738.4V
Weight770kg1100kg1430kg
Ingress protectionIP20
Anti-corrosion gradeC4-M
Operating ambient humidity5%~85%
Operating ambient temperature0°C~45°C
Max. operating altitude≤2000m
Rack cooling methodAir-cooling
Communication interfaceCAN / LAN
Communication protocolCAN2.0B / Modbus TCP

Hybrid Inverter Parameters

 Fit-110Fit-160Fit-200
Recommended max. PV array size100kW160kW200kW
Max. usable PV input power100kW160kW200kW
Max. input voltage1000V
Rated voltage620V600V
Start-up voltage180V
MPPT voltage range150V~950V
Max. input current40A x 4 / 40A x 642A x 1042A x 10
Max. short circuit current60A x 4 / 60A x 660A x 1060A x 10
Number of MPPT / Max. input strings4 MPPT / 8 strings10 MPPT / 20 strings
 Fit-110Fit-160Fit-200
Battery typeLFP  
Battery voltage range150V~950V180V~950V 
Max. charging/discharging current160A / 80A x 2200A / 100A+100A
Number of battery ports1 / 2
Max. charge/discharge current per port160A / 80A200A / 100A
CommunicationCAN / RS485
 Fit-110Fit-160Fit-200
Rated output power50kW80kW100kW
Max. apparent output power1.5 times rated power, 10s; 1.6 times rated power, 0.2s1.6 times rated power; 2 times rated power, 0.2s
Emergency switch time<10ms
Rated output voltage380V/400V/415V, 3P4W
Rated frequency50Hz/60Hz
THDu (@linear load)<3%<2%
 Fit-110Fit-160Fit-200
Max. input current182.3A243.1A300A
 Fit-110Fit-160Fit-200
Rated input voltage380V/400V/415V, 3P4W
Rated input frequency50Hz/60Hz
 Fit-110Fit-160Fit-200
Rated output power50kW80kW100kW
Max. apparent output power55kVA88kVA110kVA
Rated grid voltage380V/400V/415V, 3P4W
Rated grid frequency50Hz/60Hz
Rated grid output current76A / 72.2A / 69.6A121.5A / 115.5A / 111.3A151.9A / 144.3A / 139.1A
Power factor>0.99 (1 leading ~ 1 lagging)>0.99 (0.8 leading ~ 0.8 lagging)
THDi<3% (Linear load < 1.5%)<2%
 Fit-110Fit-160Fit-200
Max. efficiency98%97.8%
 Fit-110Fit-160Fit-200
Dimensions (W*H*D)600mm × 970mm × 290mm971.5mm × 880mm × 311mm
Weight96kg<150kg
TopologyTransformerless
Operating ambient temperature-40°C~60°C (derated over 45°C)-40°C~60°C (derated over 50°C)
Relative humidity0%~95% RH0%~100% RH
Ingress protectionIP66
Cooling methodIntelligent air cooling
Max. operating altitude4000m (derated above 2000m)4000m (derated above 3000m)
Grid connection standardEN 50549-1&2/EN 50549-10, VDE-AR-N 4105, NTS 631, CEI 0-21, C10/11, NRS 097-2-1, TOR, G99, IEC 62116, IEC 61727, MEA, PEA, etc.*
Safety/EMC standardIEC/EN 62109-1/-2, IEC/EN 61000-6-2/-4
Communication interfaceStandard: Wi-Fi + Bluetooth, CAN-BMS×1, CAN-Parallel ×2, LAN, RS485-Meter, EMS-RS485×1, CAN-EMS×1, DRM, DI×5, DO×6
Optional: 4G (alternative to Wi-Fi, WIFI is default)
Standard: WiFi + Bluetooth, CAN-BMS×2, CAN-Parallel ×2, LAN, RS485-Meter, RS485, DRM, DI×5, DO×5
Optional: 4G (alternative to Wi-Fi, WIFI is default)
*The certification standards listed in this column are planned targets. For the specific certification time, please consult with the local team.

Key Highlights

Interested in

Fit

?

Contact our team for detailed specifications, pricing, and customization options.

Message Us