Cell parameters
| Product Model | PowerM-Pro 2500/1000-400V | PowerM-Pro 3300/1700-690V | PowerM-Pro 3300/1700-800V |
| Cell type | LFP | ||
| Cell capacity | 314 / 315 Ah | ||
Pack parameters
| Product Model | PowerM-Pro 2500/1000-400V | PowerM-Pro 3300/1700-690V | PowerM-Pro 3300/1700-800V |
| Pack battery configuration | 1P104S | ||
| Pack rated energy | 104.499 / 104.832 kWh | ||
Rack parameters
| Product Model | PowerM-Pro 2500/1000-400V | PowerM-Pro 3300/1700-690V | PowerM-Pro 3300/1700-800V |
| Rack battery configuration | 1P312S | 1P416S | |
| Rack rated energy | 313.497 / 314.496 kWh | 417.996 / 419.328 kWh | |
Battery compartment parameter
| Product Model | PowerM-Pro 2500/1000-400V | PowerM-Pro 3300/1700-690V | PowerM-Pro 3300/1700-800V |
| Rated energy | 2507 kWh | 3343 kWh | |
| System battery configuration | 8P312S | 8P416S | |
| System voltage | 875.6 ~ 1107.6Vdc | 1164.8 ~ 1476.8Vdc | 1164.8 ~ 1476.8Vdc |
| Rate for charging and discharging | ≤0.5P | ||
PCS Side Parameters
| Product Model | PowerM-Pro 2500/1000-400V | PowerM-Pro 3300/1700-690V | PowerM-Pro 3300/1700-800V |
| PCS quantity | 8 | ||
| Full load voltage range | 680 ~ 1500V | 1150 ~ 1500V | 1150 ~ 1500V |
| Rated AC output voltage | 400V | 690V | 800V |
| AC output type | 3P4W | 3P3W | |
| Rated output power | 8*125kW | 8*215kW | |
| Max. output power | 8*137.5kW | 8*236.5kW | |
| Power factor | 0.99/~1 (leading) ~1 (lagging) | ||
| Total current harmonic distortion (THD) | <3% (rated power) | ||
System Parameters
| Product Model | PowerM-Pro 2500/1000-400V | PowerM-Pro 3300/1700-690V | PowerM-Pro 3300/1700-800V |
| Container dimensions (W*D*H) | 20ft.(6058 mm * 2896mm *2438 mm) | ||
| Container weight | <28t | <33t | |
| Auxiliary power supply | Self-powered | ||
| Ingress protection rating | IP55 | ||
| Anti-corrosion grade | C4/C5 (customizable) | ||
| Operating ambient temperature | -20°C ~55°C (derated over 45 °C) | ||
| Max. operating altitude | 4000m (derated above 2000m) | ||
| Cooling method | Battery compartment: liquid cooling / PCS: smart air cooling | ||
| Fire safety configuration | Aerosol + combustible gas detection + ventilation + water extinguishing system | ||
| Communication interface | LAN | ||
| Communication protocol | Modbus TCP | ||
| Certification | Battery rack: IEC 62619, IEC 63056, IEC 62477, EN 61000, UL 1973, UL 9540A, UN 38.3 PCS: IEC 62477, EN IEC 61000 | ||
Key Highlights
All-in-One Integration
Pre-integrates batteries, BMS, PCS, and EMS into a single container.
Unified AC/DC coupling for seamless operation.
Simplified & faster installation; Reduced costs & labor
Modular Design
Flexible AC voltage options for diverse applications.
Supports on-demand capacity configuration.
Independent Rack Management
Prevents performance imbalance between racks.
Maximizes overall system efficiency and extends service life.
Intelligent O&M
Real-time monitoring provides instant system visibility and diagnostics.
Rack-level control and modular design enable precise maintenance.
Related Cases
Kagoshima, Japón
2 MW / 6.7 MWh
Servicios públicos
High-precision liquid cooling and integrated safety protocols ensure consistent performance and operational security in demanding utility-scale environments.
3000 KW / 3727 KWh
Ostrich Husbandry
Engineered to withstand extreme South African heat and humidity via advanced thermal management; includes Black Start capability to safeguard delicate breeding cycles from frequent national load shedding.
400 KW / 978 KWh
Commercial Floriculture
Takes up very little space (less than 20m²) while providing essential backup power for greenhouses.